What a fire safety inspector looks for in an HMO

The short answer

An HMO fire safety inspection is really two inspections. A fire and rescue service inspecting officer enforces the Regulatory Reform (Fire Safety) Order 2005 in the shared parts of the building: the stairs, corridors, bedsit entrance doors, alarm system and the records behind them. A council environmental health officer assesses the house under the Housing Health and Safety Rating System and checks the conditions attached to the HMO licence. Both begin in the same place — a protected escape route that is clear, doors that actually close, detection and lighting that work, and paperwork that matches what is fixed to the wall.

Two inspectors, two sets of powers

The Fire Safety Order came into force on 1 April 2006 and extends to England and Wales only. In an HMO it applies to the common areas rather than the inside of each self-contained dwelling, which is why the fire and rescue authority is the enforcing authority for those shared parts.

The responsible person's core duty is to take such general fire precautions as may reasonably be required in the circumstances of the case to ensure the premises are safe. Inspecting officers can enter premises at any reasonable time, inspect the whole or part of them, and require the production of records, including plans. The government's enforcement guide describes the process as an audit, examining fire safety records as well as the premises, and confirms that inspectors' powers extend to domestic premises within HMOs.

The council's route is different. Part 1 of the Housing Act 2004 requires local housing authorities to assess hazards under the Housing Health and Safety Rating System, whose current operating guidance covers 21 potential hazards including fire. Where a category 1 hazard exists, the authority must take enforcement action; for a category 2 hazard it has a power to act rather than a duty. Before taking that action on a fire hazard in an HMO, it must consult the fire and rescue authority.

Licensing runs alongside. In England, an HMO occupied by five or more people living in two or more separate households needs a licence. A licence must include the mandatory conditions in Schedule 4 to the Act, and may include further conditions requiring facilities and equipment to be provided and kept in repair.

The escape route is examined before anything else

The Order requires routes to emergency exits, and the exits themselves, to be kept clear at all times. The manager of an HMO carries a parallel duty to keep every means of escape free from obstruction and maintained in good order and repair. Between them they cover the commonest finding: a route narrowed by bins, bikes or a wedged-open fire door.

Officers look at how the route performs, not just whether it exists. Doors must open easily and immediately, without a key or a code, and emergency lighting is required where the route needs illumination. The rating system's baseline indicators go further: egress through doors or windows should not need a key or code, and escape from bedrooms through other habitable rooms should be avoided or mitigated rather than left to an escape window.

Escape windows remain acceptable as a secondary route in a two-storey house, but the guidance treats them as a fallback, partly because they are harder for less mobile occupants to use. A bedsit behind another room, or a staircase running past an unprotected kitchen, is a design deficiency an inspector records rather than a maintenance item a landlord can fix with a screwdriver. The guide to fire and electrical hazards in rented homes sets out the same hazards from the landlord's side.

Fire doors and the fifteen-degree test

Fire doors are where inspections are won and lost. Current benchmark guidance for new buildings specifies 30-minute fire-resisting doors with smoke seals — FD30S — for the route from a flat entrance to the final exit, and 20-minute doors within protected entrance halls and stairways. Older doors may lack intumescent strips or smoke seals; whether that matters depends on the building, the door's position and the risk.

What an officer does is check that each door closes itself. Open it to roughly 15 degrees, let it go, and it should fully close and latch; repeat from the fully open position, because a badly fitted closer can fail part way through its travel. Rising butt hinges are no longer accepted as self-closing devices.

Two other findings recur. Doors of a different style often turn out to be replacements that are not fire resisting, and hollow-core doors are unlikely to provide adequate fire resistance. A fire door propped or wedged open is a failure of management as much as of hardware, since the door only does its job when it is shut.

Detection, warning, lighting and signs

Detection is specified by grade and category, and what an HMO needs depends on height, floor area and layout. The rating system's guidance expects a one- or two-storey HMO with no floor over 200 square metres to have Grade D1 to Category LD1, or LD2 in existing premises, and other HMOs — including communal areas and units of two or more rooms — to have Grade A to Category LD2, with detectors sited to BS 5839-1 for a Category L2 system. Single-room bedsits take Grade D1 to Category LD1.

The 2008 LACORS guidance recommended Grade D with LD3 coverage plus detection in kitchen, lounge and cellar for shared houses up to four storeys, and Grade A to LD2 from five or six storeys; current government guidance notes LACORS is partly out of date on domestic detection and firefighting equipment. Where they differ, the risk assessment and current guidance carry the weight.

Testing is checked as well as provision. For Grade A systems, the guidance expects at least one detector or call point in each zone tested weekly, defects logged, and a six-monthly service by a competent person; Grade D and E systems should be tested monthly with the test button, and detectors tested against smoke at least annually. Emergency escape lighting, where fitted, should be tested monthly by simulating failure of the supply, illuminate for three hours, and undergo an annual discharge test.

Signage is more limited than landlords expect. Fire exit signs are normally needed only where there are alternative routes, a secondary exit by external stair, a roof-level route, or real potential for confusion; single-staircase buildings usually need none. Doors across the escape route and communal room doors should carry "fire door keep shut" signs, and store, plant and electrical cupboard doors "fire door keep locked shut". Fire action notices are generally required in the common areas of an HMO.

The records the officer will ask for

A licensed HMO is one of the cases where the Order requires the risk assessment to be recorded. The responsible person must record the significant findings and the measures taken, and must record the fire safety arrangements, where a licence under an enactment is in force. In practice the officer reads the assessment against the building, looking for findings specific to it rather than a generic template.

Certificates come next. The manager must supply the latest gas appliance test certificate within seven days of a written request, and ensure every fixed electrical installation is inspected and tested at intervals not exceeding five years, with a certificate produced. Licence conditions add a declaration, on demand, that electrical installations are safe and in working order, appliances and furniture are safe, and smoke alarms are fitted on each storey used as living accommodation, with carbon monoxide alarms where fixed combustion appliances are present.

Portable appliance testing is where landlords most often misread the duty. The 2008 guidance says appliances should be checked at the start of each tenancy, that regular checking afterwards is good practice, and that there is no legal requirement to do so unless the appliances are used by employees. Current rating-system guidance expects landlord-supplied appliances to be tested in line with the IET Code of Practice unless they are under a year old and carry a UKCA or CE mark. The licence condition requires appliances to be kept safe. A dated PAT record is the simplest evidence that all three are satisfied, which is why inspectors ask for it, and the essential guide to PAT testing for landlords explains what a test actually covers.

Everything else hangs off maintenance. Facilities, equipment and devices provided under the Order must be kept in efficient working order and good repair. Where extinguishers are provided they should be serviced annually to BS 5306-3, and a property logbook recording routine maintenance, defects and remedial action is the document that turns a pile of certificates into a defensible record. For landlords working through this list for the first time, HMO compliance testing brings the appliance testing, alarm servicing, emergency lighting and fire risk assessment together in one visit.

Extinguishers are a genuine difference of view. The 2008 guidance recommends a multi-purpose extinguisher on each floor of the common parts. Current rating-system guidance says extinguishers are not normally considered necessary in the common parts of HMOs or blocks of flats, because residents rarely receive training, though they remain appropriate in plant rooms. The Order requires equipment only where the risk assessment shows it is necessary.

What happens when something is wrong

Most visits end in advice. Where breaches are minor and the responsible person is plainly trying, the enforcement guide expects verbal advice; more significant but low-risk breaches may produce a non-statutory notice listing each article breached and the action suggested. A statutory enforcement notice sets a timescale of at least 28 days, and a prohibition notice restricts or prohibits use where there is an urgent need to protect people.

Prosecution is reserved for breaches that put people at risk of death or serious injury. The maximum penalty is an unlimited fine and, at the Crown Court, up to two years' imprisonment. The council has its own ladder — improvement notice, prohibition order or hazard awareness notice — and, for a category 1 hazard with imminent risk, emergency remedial action or an emergency prohibition order.

For a landlord or managing agent the lesson is that the inspection is evidence-led: a tidy building with no records fares worse than a plain building with a current risk assessment, alarm test log, wiring certificate and gas certificate. The officer is not looking for perfection, only a route that works, doors that close, detection that is tested, and paper that proves it.

If you manage HMOs in Northamptonshire, Leicestershire, Buckinghamshire or Bedfordshire, PatTest.com carries out PAT testing, fire alarm servicing, emergency light testing and fire risk assessments for HMOs, and issues the certificates and assessment in PDF form so the file is ready before the officer arrives.